Home / Guides / Fire safety inspection checklist
Guides · Fire Protection

The fire safety inspection checklist.

The short version: the business permit is not renewed without a Fire Safety Inspection Certificate (FSIC), and the FSIC comes after a BFP inspector walks the building. Most renewals fall in January, so inspections and orders run from November to January. This page lists the equipment the inspector looks at — extinguishers, fire hose and hose cabinets, emergency lights, exit signs, smoke detectors, sprinkler heads and valves — what passes, and a tick-list to print and walk the building with before the visit. RA 9514 (the Fire Code) and its IRR govern; the inspector's findings for your building are final.

Fire protection supply →

How the inspection fits the permit renewal

Plain summary · steps vary slightly by LGU

StepWhat happens
1. File the renewalAt the city or municipal business permit office, usually within the first 20 days of January; the fire code fees are assessed with it
2. BFP inspectionAn inspector checks the equipment and exits below against the Fire Code and the occupancy of the building
3. Notice to ComplyIf anything is missing, expired or not working, the BFP lists it with a period to correct it, then re-inspects
4. FSIC issuedWith the FSIC the LGU releases the permit; keep it posted on the premises

Equipment has to be on the wall, tagged and working on the day — an item on order does not pass. Ordering in November leaves time for delivery and installation before the January rush.

The tick-list

Walk the building with this · tick what passes · order what does not

Fire extinguishers

✓ItemWhat the inspector checksIf it fails, order
Extinguisher on every floor and in each areaNone farther than 23 m walking distance from any point; at least one per floor; nothing blocking itABC dry chemical, 10 lb, Spiderking dry chemical
Right class for the hazardCO2 or clean agent at panels, generators and server rooms; Class K at commercial kitchens; ABC for general areasSpiderking HCFC clean agent
Gauge in the green, pin and seal in placePressure gauge needle in the green band; safety pin and tamper seal intact; hose not crackedRecharge, or a replacement unit
Maintenance tag in dateAnnual service tag with date and servicing company; hydrostatic test date within 12 years for dry chemical, 5 years for CO2Service, or a replacement unit
Mounted and signedOn a bracket or cabinet, top no higher than about 1.5 m, with a sign showing where it isBrackets, cabinets and signs with the order

Fire hose and hose cabinet

✓ItemWhat the inspector checksIf it fails, order
Hose cabinet at each standpipe outletCabinet on every floor where the building has a standpipe; door opens, not locked or blocked, glass or label marked FIRE HOSEFire hose cabinet
1-1/2 in hose, racked and connectedOccupant-use hose connected to the valve, folded on the rack, no rot, mildew, cuts or kinks; coupling tight1-1/2 in × 50 ft single-jacket hose, hose rack nipple
Nozzle on the hoseNozzle present and the right thread; not missing or swapped for a garden nozzleFire hose nozzle
Hose valve opens and does not leakAngle valve turns by hand, no drip at the stem or the hose connectionFire hose valve
2-1/2 in outlet for the fire serviceWhere the standpipe has a fire-department outlet, the valve is capped and reachable2-1/2 in × 50 ft double-jacket hose

Emergency lights and exit signs

✓ItemWhat the inspector checksIf it fails, order
Emergency light on the exit routeLights corridors, stairs and exit doors; test button works; battery runs at least 90 minutesOmni AEL-390, Omni AEL-190
Exit sign over every exit doorLit and readable, at each exit and at each turn where the exit is not in sight; arrow points the right wayLED exit sign, single face, double face, with arrow
Exit sign stays lit on power failureBattery-backed; still lit when the breaker is switched offExit sign and emergency light combo
Exits clear and doors unlockedNo stock in corridors or stairs; exit doors open from inside without a key; fire doors close on their ownNo purchase — clear and re-sign the route

Smoke detectors and fire alarm

✓ItemWhat the inspector checksIf it fails, order
Smoke detector where the occupancy calls for oneRooms where people sleep (dormitories, hotels, staff quarters) and as the alarm plan requires; not painted, bagged or coveredStandalone photoelectric smoke detector, 10-year sealed-battery alarm
Heat detector in kitchens and garagesHeat, not smoke, where cooking or exhaust would set off false alarmsConventional heat detector
Detectors wired to the panel testTest button or smoke test sounds the alarm; panel shows no trouble or fault lightConventional smoke detector with base, 4-zone panel
Pull station and bellManual pull station at exits, bell or horn heard throughout the floorManual pull station, fire alarm bell, horn strobe

Sprinkler heads and valves

✓ItemWhat the inspector checksIf it fails, order
Sprinkler heads clean and clearNot painted, corroded, taped or loaded with dust; at least 457 mm (18 in) clear between the deflector and stored goodsSprinkler heads, concealed sprinklers
Spare-head cabinetAt least 6 spare heads for up to 300 sprinklers, 12 up to 1,000, 24 above that, each type and temperature, with the sprinkler wrenchSpare heads matched to the installed type
Control valves open and supervisedRiser gate and butterfly valves fully open, sealed or fitted with a tamper switchOS&Y gate valve, UL/FM, grooved butterfly valve with tamper switch
Alarm and check valves workingAlarm check valve trims and gauges in place; check valve holds; water-flow alarm sounds on the inspector’s testAlarm check valve, grooved swing check valve, UL
Fire department connectionSiamese connection outside, capped, signed and not blocked by parking or plantersSiamese twin connection

Sprinkler and alarm repairs beyond swapping heads and valves are done by the fire-protection contractor who maintains the system; the BFP asks for their maintenance report.

Extinguisher by class

Which unit goes where · common sizes

ClassFireAgentCommon sizeWhere
AWood, paper, cloth, plasticABC dry chemical10 lbOffices, stores, classrooms, corridors
BFuel, oil, paint, solventABC dry chemical, foam or CO220 lbGenerators, fuel stores, garages, workshops
CLive electrical equipmentCO2 or clean agent (HCFC)10 lbPanel rooms, server rooms, control rooms
KCooking oil and fatWet chemical6 LCommercial kitchens with fryers

What to send for a quote

Everything on this list is stocked or sourced from Dasmariñas, Cavite — Drychem and Spiderking extinguishers, fire hose, cabinets, hose valves and nozzles, Omni emergency lights and exit signs, Dahua detectors and alarm panels, sprinkler heads and UL/FM valves — and delivered nationwide. Send the list or the Notice to Comply and we quote it back the same day.

Common questions

Do I need a Fire Safety Inspection Certificate to renew my business permit?

Yes. Under RA 9514 the LGU does not release a new or renewed business permit until the BFP issues the Fire Safety Inspection Certificate (FSIC) for the premises. Renewals fall in the first weeks of January in most LGUs, so the inspection and any repairs are best done in November and December.

What happens if the inspector finds something missing?

The BFP issues a Notice to Comply listing the defects and the period to correct them. Once the items are in place the building is re-inspected and the FSIC follows. Fixing the list before the visit avoids the second trip and the delay on the permit.

How many fire extinguishers does a shop or office need?

The Fire Code IRR follows NFPA 10: at least one per floor, none farther than 23 m walking distance from any point for ordinary (Class A) fires, plus a unit sized for the hazard at every kitchen, generator, fuel store and electrical room. The inspector confirms the count for your floor area and occupancy.

Which extinguisher for an electrical room or a kitchen?

Electrical rooms, panels and server rooms take CO2 or a clean-agent (HCFC) unit, which leaves no powder on the equipment. Commercial kitchens with deep fryers take a Class K wet-chemical unit. ABC dry chemical covers most other areas.

How long must emergency lights stay on?

At least 90 minutes on battery after the power fails, lighting the exit route, stairs and exit doors. The inspector presses the test button, so a unit with a dead battery fails even if it lights on mains power.

How many spare sprinkler heads should a building keep?

NFPA 13, as adopted by the Fire Code, asks for a spare-head cabinet with at least 6 heads for up to 300 sprinklers, 12 for 300 to 1,000 and 24 for more than 1,000, covering each type and temperature rating installed, plus the sprinkler wrench.

What does Southend supply from this list?

Extinguishers (ABC dry chemical, HCFC clean agent), fire hose, hose cabinets, hose valves and nozzles, emergency lights, exit signs, smoke and heat detectors, alarm bells, pull stations and panels, sprinkler heads, UL/FM gate, butterfly, check and alarm check valves, and siamese connections, from Dasmariñas, Cavite with nationwide delivery. Send the list for a Same-Day Quote.

Related

Fire protection supply →Guide: the safety kit a construction site holds →Electrical supply →Valves →All guides →

Standards referenced. RA 9514 (Fire Code of the Philippines) and its Revised IRR · NFPA 10, 13, 14, 72 and 101 as referenced by the IRR. This page is a planning and ordering list, not a fire safety evaluation — the BFP inspector's findings and the building's approved fire-protection plan govern.