Home / Guides / Circuit breaker guide
Guides · Electrical Supply

Choosing a circuit breaker.

A breaker protects the wire, not the appliance — so breaker and wire size are chosen together, per the Philippine Electrical Code. The table below is the common pairing on 230V residential work. Panel schedules and final sizing are the licensed electrician's job; this page is for reading them and ordering right.

Browse electrical supply →

Breaker and wire go together

Typical pairings · THHN copper · 230V single-phase per the PEC

CircuitWire (THHN copper)Breaker
Lighting2.0 mm²15 A
Convenience outlets3.5 mm²20 A
Window aircon, dedicated3.5 mm²20 A
Split-type aircon / water heater5.5 mm²30 A
Electric range8.0 mm²40 A
Small feeder / sub-panel14 mm²60 A

Typical pairings only — run length, conduit fill, ambient temperature and actual load all adjust the numbers. The panel schedule from a licensed electrician or electrical engineer governs.

Plug-in or bolt-on

The two mounting types are not interchangeable — match the panel. Plug-in breakers snap onto the bus bar and are the common residential type. Bolt-on breakers screw to the bus for a firmer, vibration-proof connection and are the usual requirement on commercial projects and inspected installations. Both are stocked, single- to three-pole.

Reading the rating

Ground-fault protection

Bathrooms, kitchen counters, laundry areas, garages and outdoor outlets need ground-fault protection — a GFCI outlet on the branch or an RCBO in the panel. It trips on milliamperes of leakage to protect people, which an ordinary thermal-magnetic breaker never sees.

Common questions

What breaker size for an aircon?

A window-type unit around 1HP typically runs on a dedicated 20A circuit on 3.5mm² wire. Split-type and bigger units go by the nameplate current — dedicated circuit, breaker and wire sized together per the Philippine Electrical Code.

My breaker keeps tripping — can I put a bigger one?

No. The breaker is sized to protect the wire, not to keep the load running. A bigger breaker on the same wire lets the wire overheat before the breaker trips — that is how electrical fires start. Find the cause: overload, loose termination or a fault.

What does 20AT/50AF mean?

AT is the ampere trip — the current where it trips (20A). AF is the ampere frame — the physical frame's maximum rating (50A). Panel schedules list both; match AT to the circuit and AF to the panel provision.

Plug-in or bolt-on breaker?

Whichever your panel takes — they are not interchangeable. Plug-in breakers snap onto the bus and are common in residential panels; bolt-on breakers screw to the bus for a firmer connection and are the usual requirement on commercial and inspected work.

Where is ground-fault protection required?

Wet and grounded locations: bathrooms, kitchen counters, laundry, garages and outdoor outlets. Use a GFCI outlet or an RCBO in the panel per the Philippine Electrical Code.

Related

Electrical supply Fire protection Guide: site PPE checklist All guides

Reviewed July 2026 · Southend Construction & Industrial Supplies, Dasmariñas, Cavite